On an open tank level measurement the L.P. side is
vented to atmosphere. Whatever pressure acts is on the H.P. side which is a
measure of level.
This blog is about instrumentation and control engineering with all information related to plant process,Equipments,field and control instrumentsprojects, seminars, job vacancies and subject theories
FIELD INSTRUMENTS
Tuesday, February 18, 2014
Sunday, February 16, 2014
Three way manifold valve operation:
Three way manifold valve operation:
- The following photograph shows a three-valve manifold bolted to a Honeywell model ST3000 differential pressure transmitter.
- A bleed valve fitting may be seen inserted into the upper port on the nearest diaphragm capsule flange.
- In normal operation, the two block valves are left open to allow process fluid pressure to reach the transmitter.
- The equalizing valve is left tightly shut so no fluid can pass between the “high” and “low” pressure sides.
- To isolate the transmitter from the process for maintenance, one must close the block valves and open the equalizing valve.
- The best sequence to follow is to first close the high-pressure block valve, then open the equalizing valve, then close the low-pressure block valve.
- This sequence ensures the transmitter cannot be exposed to a high differential pressure during the isolation procedure, and that the trapped fluid pressure inside the transmitter will be as low as possible prior to “venting” to atmosphere.
- Finally, the “bleed” valve is opened at the very last step to relieve pent-up fluid pressure within the manifold and transmitter chambers.
Instrument calibration
Instrument calibration
Calibration and ranging are two tasks associated with establishing an accurate correspondence between any instrument’s input signal and its output signal.
To calibrate an instrument means to check and adjust its response so the output accurately corresponds to its input throughout a specified range.
In order to do this, one must expose the instrument to an actual input stimulus of precisely known quantity.
For a pressure gauge, indicator, or transmitter, this would mean subjecting the pressure instrument to known fluid pressures and comparing the instrument response against those known pressure quantities.
One cannot perform a true calibration without comparing an instrument’s response to known, physical influence or impact.
To range an instrument means to set the lower and upper range values (LRV & URV), so it responds with the desired sensitivity to changes in input.
For example, a pressure transmitter set to a range of 0 to 200 PSI (0 PSI = 4 mA output ; 200 PSI = 20 mA output) could be re-ranged to respond on a scale of 0 to 150 PSI (0 PSI = 4 mA ; 150 PSI = 20 mA).
In analog instruments, re-ranging could only be accomplished by re-calibration, since the same adjustments were used to achieve both purpose (i.e. Flow measurement).
In digital instruments, calibration and ranging are typically separate adjustments (i.e. it is possible to re-range a digital transmitter without having to perform a complete re-calibration), so it is important to understand the difference, As smart Transmitters using HART or FOUNDATION FIELDBUS protocols.
Calibration and ranging are two tasks associated with establishing an accurate correspondence between any instrument’s input signal and its output signal.
To calibrate an instrument means to check and adjust its response so the output accurately corresponds to its input throughout a specified range.
In order to do this, one must expose the instrument to an actual input stimulus of precisely known quantity.
For a pressure gauge, indicator, or transmitter, this would mean subjecting the pressure instrument to known fluid pressures and comparing the instrument response against those known pressure quantities.
One cannot perform a true calibration without comparing an instrument’s response to known, physical influence or impact.
To range an instrument means to set the lower and upper range values (LRV & URV), so it responds with the desired sensitivity to changes in input.
For example, a pressure transmitter set to a range of 0 to 200 PSI (0 PSI = 4 mA output ; 200 PSI = 20 mA output) could be re-ranged to respond on a scale of 0 to 150 PSI (0 PSI = 4 mA ; 150 PSI = 20 mA).
In analog instruments, re-ranging could only be accomplished by re-calibration, since the same adjustments were used to achieve both purpose (i.e. Flow measurement).
In digital instruments, calibration and ranging are typically separate adjustments (i.e. it is possible to re-range a digital transmitter without having to perform a complete re-calibration), so it is important to understand the difference, As smart Transmitters using HART or FOUNDATION FIELDBUS protocols.
What is LNG?
•LNG
is natural gas cooled to -161o Centigrade, the temperature at which its main
component, methane, liquefies.
•Its
volume is reduced to around one six-hundredth of its volume as a gas
•It is
stored and transported at atmospheric pressure as a boiling liquid
•It is
an odorless, colorless liquid
.
Saturday, February 15, 2014
What is pressure?
Pressure: It is defined as Force per unit Area. P = F/A
Units : bar, Pascal, kg / cm2, lb / in2.
PRESSURE CONVERSIONS
PRESSURE CONVERSIONS :
1psi =
|
27.74 " H2O
|
1 Kg/cm2 =
|
14.223 psi
|
1 Bar =
|
14.504 psi
|
1 Kpa =
|
0.145 psi
|
1 Kg/cm2 =
|
10.000mm of H20
|
1 Bar =
|
1.0197 Kg/cm2
|
1 Kg/cm2 =
|
0.98 Bar
|
1 Torr =
|
1 mm of Hg.
|
Subscribe to:
Posts (Atom)



